Manufacture: Telemecanique
Type: Motor Circuit Breaker
Model: GV2ME08
Product name: TeSys GV2
Device short name: GV2ME
Device application: Motor
Thermal protection adjustment range: 2.5 … 4 A
Magnetic tripping current: 51 A
Rated operational voltage Ue: 690 V AC 50/60 Hz IEC 60947-2
Rated insulation voltage Ui: 690 V AC
Frequency: 50/60 Hz
Motor power: 1.1 KW 400/415 V AC 50/60 Hz, 1.5 KW 400/415 V AC 50/60 Hz
Breaking capacity: 100 KA Icu 400/415 V AC 50/60 Hz IEC 60947-2
Conventional free air thermal current Ith: 4 A IEC 60947-4-1
Rated impulse withstand voltage Uimp: 6 kV
Power dissipation per pole: 2.5 W
Standard: IEC / EN 60947-2, IEC / EN 60947-4-1
Poles description: 3P
Line Rated Current: 4 A
Degree of protection: IP20
Ambient air temperature for operation: -20 … 60 °C
Dimensions: 89 x 45 x 78.5 mm